10.1.10 Data link is disabled on a station of a Basic model QCPU or
Data link is disabled on a Basic model
QCPU or safety CPU station.
Has a LINK PARA. ERROR
occurred in a Basic model
QCPU, or a NETWORK
PARAMETER ERROR
in a safety CPU?
No
End
Is the CC-Link IE Controller
Network module's function
version D or later?
Yes
Yes
Is the Basic model QCPU's
function version B or later?
Use a CC-Link IE Controller Network module of
function version D or later.
Use a Basic model QCPU of function version B
or later.
No
No
Yes
Check the network parameters.
Check the own station send range in LB/LW of
the Basic model QCPU and the safety CPU
station in the network range assignment setting
for the control station.
Cyclic transmission is disabled