525
CHAPTER 10 TROUBLESHOOTING
10
10.2 Error Codes
10.2.2 Error code list
E521
H
to
E524
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
E5D1
H
to
E5D5
H
E5E1
H
to
E5E9
H
E5F0
H
Transient execution error (no
baton passing on the target
station)
Transient transmission was
executed while the target
station did not perform baton
(or token) passing.
• Reconnect the target station to the network.
• Execute the dedicated instruction, interlocking with
Baton pass status (own station) (SB0047) and Baton
pass status of each station (SW00A0 to SW00A7).
• Check the Cause of baton pass interruption (SW0048)
at another station and restart baton (or token) passing
before executing the transient transmission.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
E5F1
H
Specified station No.
duplication error
The station No. specified for
the transient transmission is
duplicated.
• Change the station No. of the normal station.
E5F2
H
to
E5F7
H
Network module error The hardware has failed.
• Please consult your local Mitsubishi representative.
EA00
H
to
EA04
H
EA10
H
to
EA18
H
EAE0
H
to
EAE4
H
EAE5
H
CPU module error
Incorrect data have been set
in the CPU.
EAE6
H
CC-Link IE Controller
Network-incompatible CPU
error
The CPU module is not
compatible with the CC-Link
IE Controller Network
module.
• Use a CPU module that is compatible with the CC-Link
IE Controller Network module. ( Page 40,
Section 2.3)
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
EAE7
H
Network module error The hardware has failed. • Please consult your local Mitsubishi representative.
EAF0
H
to
EAF6
H
F000
H
to
FEFF
H
Errors detected in the MELSECNET/H or MELSECNET/10 network system.
( Troubleshooting in the MELSECNET/H or MELSECNET/10 Network System Reference Manual)
Error code Error Error detail Corrective action