538
(a) H/W LED information
Item Description
RUN
Displays the operating status of a module.
0001: Operating normally
0000: Hardware fault or watchdog timer error
PLC
Displays the network type.
0001: Controller network
ONLINE
Displays the operation mode of the CC-Link IE Controller Network module.
0001: Online mode
0000: Other than online mode
TEST
Displays the operation mode of the CC-Link IE Controller Network module.
0001: Test mode
0000: Other than test mode
OFFLINE
Displays the operation mode of the CC-Link IE Controller Network module.
0001: Offline mode
0000: Other than offline mode
M/S. ERR.
Displays the detection status of duplicated control station or station No.
Check the network status by CC IE Control diagnostics. ( Page 541, Section 10.4)
0001: Duplicated control station or station No. detected
0000: Undetected
PARAM.ERR.
Displays the parameter error detection status.
Check the network status by CC IE Control diagnostics. ( Page 541, Section 10.4)
0001: Parameter error detected
0000: Undetected
F LOOP ERR.
Displays the IN-side error detection of the CC-Link IE Controller Network module.
Check the network status by CC IE Control diagnostics. ( Page 541, Section 10.4)
0001: IN-side error detected
0000: Undetected
MANAGER
Displays the station type of the CC-Link IE Controller Network module.
0001: Control station is operating
0000: Other than control station is operating
SUB MANAGER
Displays the station type of the CC-Link IE Controller Network module.
0001: Sub-control station is operating
0000: Other than sub-control station is operating
NORMAL
Displays the station type of the CC-Link IE Controller Network module.
0001: Normal station is operating
0000: Other than normal station is operating
TOKEN PASS
Displays the baton pass status of the CC-Link IE Controller Network module.
0001: Baton pass being executed
0000: Baton pass unexecuted
DATA LINK
Displays the data link status of the CC-Link IE Controller Network module.
0001: Data link being executed
0000: Data link not executed
R LOOP ERR.
Displays the OUT-side error detection of the CC-Link IE Controller Network module.
Check the network status by CC IE Control diagnostics. ( Page 541, Section 10.4)
0001: OUT-side error detected
0000: Undetected
EXT. POWER
Displays the external power supply status, of the CC-Link IE Controller Network module with
external power supply function.
0001: External power supplied
0000: No external power supplied