539
CHAPTER 10 TROUBLESHOOTING
10
10.3 CC IE Control Diagnostics
10.3.4 System monitor
(b) H/W switch information
Item Description
NET WORK NO. Displays the network No. of the CC-Link IE Controller Network module. (Range: 1 to 239)
GROUP NO. Displays the group No. of the CC-Link IE Controller Network module. (Range: 1 to 32)
STATION NO. Displays the station No. of the CC-Link IE Controller Network module. (Range: 1 to 120)
MODE
Displays the operation mode of the CC-Link IE Controller Network module.
0: Online
2: Offline
5: Station-to-station test
6: Circuit test
7: Self-loopback test
9: Hardware test
CONFIG.
Displays the configuration of the CC-Link IE Controller Network module.
b15b14 b3b4b5b6 b2 b1 b0
SW0044
0to
to
000
Network type
(01: Controller network)
Station type
(0: Normal station, 1: Control station)
CPU type
0: Other than Basic model QCPUs and
safety CPUs
1: Basic model QCPU or safety CPU
Mode
0: CC IE Control
1: CC IE Control Extended Mode
Normal station parameter
0: No normal station parameter
1: Normal station parameter