CHAPTER 4 FUNCTIONS
4
4.1 Cyclic Transmission Function
4.1.11 Interlink transmission
4.1.11 Interlink transmission
Link device (LB/LW) data of a network module are transferred to another network module through a relay station.
Interlink transmission is executable between CC-Link IE Controller Network, MELSECNET/H and CC-Link IE Field
Network.
(1) Setting the link device transfer range
Set the link device transfer range in "Interlink Transmission Parameters" in the "MELSECNET/CC IE/Ethernet
Module Configuration" window of the relay station. ( Page 232, Section 6.8)
(2) An example of interlink transmission
The following is an example of interlink transmission between network No.1 and network No.2.
1. B0 turns ON on 1M
P
1.
2. By cyclic transmission, 1N
S
3 receives LB0 data.
3. The received LB0 data are transferred to LB1000 on 2M
P
1 by interlink transmission.
4. By cyclic transmission, 2N
S
2 and 2N
S
3 receive LB1000 data.
Data of network No.2
CPU module
Power supply module
Network
module 1
Interlink
transfer
Network
module 2
Network No.1
Data of network No.1
Network No.2
LB LB
CPU module
1M
P1
1N
S2
1N
S3
1N
S3
2M
P1
2M
P1
2N
S2
2N
S3
0
3FF
13FF
1FFF
1000
LB LB
3.
2.
B
1000 to 101F
1020 to 103F
100 to 11F
200 to 21F
1300 to 131F
0 to 1F
1M
P11NS22NS22NS3
Network No.1
Network No.2
Link refresh
range
Transfer target link
devices do not turn
ON/OFF because they
are not set within the
link refresh range.
B1300
B200 B1000
B0
B280
B281
B1000
4. 5.
B1300
1.
B0
B200

Table of Contents

Other manuals for Mitsubishi Electric MELSEC-Q Series

Related product manuals