5 REPLACEMENT OF BASE UNIT AND EXTENSION CABLE
5 - 17
When replacing the Ans/QnA series with the Q series, this product can be replaced by using the existing
wiring on the installation space that is the same as existing installation space.
5.5.1 Specifications
(1) AnS size Q series large type main base unit
(2) AnS size Q series large type extension base unit (type requiring power supply module)
5.5 AnS Size Q Series Large Type Base Unit
Item
Model
Q35BLS Q38BLS Q35BLS-D Q38BLS-D
Number of mountable I/O
modules
5858
Extendability Mounting additional stages is possible.
Applicable module Q series module
Internal current
consumption (5VDC)
0.11A 0.12A 0.11A 0.12A
Mounting hole size 6 hole (For M5 screw) –
External
dimensions
H 130mm 118mm
W 325mm 430mm 311mm 416mm
D 53mm 48.5mm
Weight 0.82kg 1.32kg 0.59kg 0.72kg
DIN rail installation Cannot be installed. Can be installed.
Item
Model
Q65BLS Q68BLS Q65BLS-D Q68BLS-D
Number of mountable I/O
modules
5858
Extendability Mounting additional stages is possible.
Applicable module Q series module
Internal current
consumption (5VDC)
0.11A 0.12A 0.11A 0.12A
Mounting hole size 6 hole (For M5 screw) –
External
dimensions
H 130mm 118mm
W 315mm 420mm 304mm 409mm
D 53mm 48.5mm
Weight 0.98kg 1.32kg 0.57kg 0.74kg
DIN rail installation Cannot be installed. Can be installed.