7 REPLACEMENT OF PROGRAM
7 - 29
*1 For the number of mountable CC-Link modules and the number of settable parameters with the software package, refer to
the CC-Link System Master/Local Module User's Manual.
PLC RAS setting
WDT setting
WDT setting ï‚¡
Initial execution monitoring time ï‚¡
Low speed execution monitoring time ï‚´ The Universal model QCPU does not support the low speed program.
Error check
Carry out battery check ï‚¡
Carry out fuse blown check ï‚¡
Carry out I/O module comparison ï‚¡
Operation mode when
there is an error
Computation error ï‚¡
Expanded command error ï‚¡
Fuse blown ï‚¡
I/O module comparison error ï‚¡
Special module access error ï‚¡ The name changes to "Intelligent module program execution error".
Memory card access error ï‚¡
Memory card operation error ï‚¡
Constant scanning ï‚¡
Annunciator
display mode
F No. display ï‚´ The QCPU does not incorporate this display function.
Comment display ï‚´ The QCPU does not incorporate this display function.
Occurrence time ï‚´ The QCPU does not incorporate this display function.
Break down
history
Drive ï‚¡
The storage location in the Universal model QCPU is fixed, therefore this setting does
not exist.
File name ï‚¡
History No. ï‚¡
Low speed program execution time ï‚´ The Universal model QCPU does not support the low speed program.
I/O assignment Reviewing is required if the Q series CPU base unit has other than 8 slots.
Boot file setting ï‚¡
Program setting ï‚¡
SFC setting
SFC program start mode ï‚¡
Start conditions ï‚¡
Output mode when the block is stopped ï‚¡
Network parameter
MELSECNET (II), /B ï‚´
Parameters are deleted, since the Q series CPU is not compatible with the
MESECNET (II), /B.
MELSECNET/10 (H) ï‚¡ Converted to the MELSECNET/10 mode.
MELSECNET/MINI ï‚´
Parameters are deleted, since the QCPU is not compatible with the MELSECNET/
MINI.
CC-Link ï‚¡
The number of settable parameters with the software package is eight.
*1
Set the parameters of the ninth module or later with dedicated instructions.
Ethernet ï‚¡
The "Use the KeepAlive" of "TCP Existence confirmation setting" in the "Ethernet
operations" is automatically set.
Name
Compat-
ibility
Remarks