3 REPLACEMENT OF I/O MODULE
3 - 2
Input module
A1SX30 (24VDC,
positive common)
QX40
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.8.5mA Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: not changed
A1SX30 (24VDC,
nagative common)
QX80
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.8.5mA ï‚® Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: not changed
A1SX30
(12VDC)
QX70
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.4mA ï‚® Approx.3.3mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: not changed
A1SX30
(12VAC, 24VAC)
(None)
Convert 12VAC or 24VAC to DC externally before input to the QX40/QX80 (24VAC)
or QX70 (12VAC).
A1SX40
(24VDC)
QX40
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.7mA ï‚® Approx.4mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: not changed
A1SX40
(12VDC)
QX70
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.3mA ï‚® Approx.3.3mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: not changed
5) Function: not changed
A1SX40-S1 QX40-S1
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: not changed
4) Specifications
Rated input voltage: not changed
Rated input current: changed (Approx.7mA ï‚® Approx.6mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: not changed
AnS/QnAS series model Q series alternative model
Product Model Model Remarks (restrictions)