11 USING A DIRECT DRIVE MOTOR
11.2 Startup [G] [WG]
Setting of identification signal amplitude by minute position detection method
If [AL. 032 Overcurrent], [AL. 050 Overload 1], [AL. 051 Overload 2], or [AL. 0E1 Overload warning 1] occurs at the magnetic
pole detection by the minute position detection method, set a smaller value for [Pr. PL18 Magnetic pole detection - Minute
position detection method - Identification signal amplitude]. Basically, [Pr. PL18] does not need to be changed from the initial
value.
Operation at magnetic pole detection
Precautions
After the magnetic pole detection, check the positioning accuracy with the test operation (positioning operation function) of
MR Configurator2.
The magnetic pole detection improves in accuracy when performed with no load.