11 - 30
11. OPTIONS AND PERIPHERAL EQUIPMENT
(a) When using the 600V Polyvinyl chloride insulated wire (IV wire)
Selection example of wire size when using IV wires is indicated below.
Table 11.1 Wire size selection example 1 (IV wire)
Servo amplifier
Wires [mm
2
] (Note)
1) L
1
L
2
2) 24V 0V 3) U V W 4) PC 5) B1 B2
MR-JN-10A(1)
2(AWG14) 2(AWG14) 2(AWG14) 2(AWG14) 1.25(AWG16)
MR-JN-20A(1)
MR-JN-40A
Note. Wires are selected based on the highest rated current among combining servo motors.
(b) When using the 600V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Selection example of wire size when using HIV wires is indicated below.
Table 11.2 Wire size selection example 2 (HIV wire)
Servo amplifier
Wires [mm
2
] (Note 1)
1) L
1
L
2
2) 24V 0V 3) U V W 4) PC 5) B1 B2
MR-JN-10A(1)
2(AWG14)
(Note 2)
2(AWG14)
(Note 2)
2(AWG14)
(Note 2)
2(AWG14) 1.25(AWG16)
MR-JN-20A(1)
MR-JN-40A
Note 1. Wires are selected based on the highest rated current among combining servo motors.
2. If compliance with the National Electrical Code is not required, a wire size of 1.25mm
2