13. POSITIONING MODE
13.2 Signals
13.2.1 I/O signal connection example
LZ
Plate
Servo amplifier
(Note 1)
(Note 2)
Trouble (Note 6)
Electromagnetic
brake interlock
9ALM
10
MEND
11 RD
12 MBR
(Note 7)
CN1
Travel completion
(Note 13)
Ready
15 LA
16 LAR
17 LB
18 LBR
14 LG
21 OP
SD
10m max.
2m max.
Encoder B-phase pulse
(differential line driver)
Control common
Encoder Z-phase pulse
(open collector)
Encoder Z-phase pulse
(differential line driver)
19
20 LZR
(Note 7)
CN1
1
13
DICOM
DOCOM
10m max.
+
CN3
(Note 8)
MR Configurator
Personal
computer
24VDC
RA1
RA2
RA3
RA4
(Note 4, 9)
(Note 9, 11)
8
4
3
7
Forced stop
Servo-on
Automatic/manual selection
Forward rotation start
Reverse rotation start
(Note 3, 5)
25
6
Proximity dog
EM1
SON
MD0
ST1
ST2
DOG
(Note 9,
10, 12)
5DI0
23DI1
Point table No./Program No.
selection 2
Point table No./Program No.
selection 1
CNP1
2OPC
Control common
Encoder A-phase pulse
(differential line driver)
USB cable
(option)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the (terminal marked ) servo amplifier to
the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24VDC±10% 200mA current for interfaces from the outside. 200mA is the value applicable when all I/O signals are
used. The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.8.2 (1) that gives the
current value necessary for the interface.
5. When starting operation, always turn on the forced stop (EM1). (Normally closed contact)
6. Trouble (ALM) turns on in normal alarm-free condition. (Normally closed contact)
7. The pins with the same signal name are connected in the servo amplifier.
8. Use MRZJW3-SETUP221E (Software version C4 or later).
9. For sink I/O interface. For source I/O interface, refer to section 3.8.3. However, pin 23 and pin 25 cannot be used at the source
interface.
10. The assigned signals can be changed using parameter No. PD02, PD04, PD06, PD08, PD10, PD12, or PD14.
11. The assigned signals can be changed using parameter No.PD15 to PD18.
12. The forward rotation stroke end (LSP) and the reverse rotation stroke end (LSN) automatically switch ON if not assigned to the
external input signals.
13. Set "
24 " in parameter No. PD16 to assign travel completion (MEND).