13. POSITIONING MODE
(3) Command system
Make selection with the input signals from among the point tables that have been set in advance, and
perform operation with Forward rotation start (ST1) or Reverse rotation start (ST2). Automatic operation
has the absolute value command system and incremental value command system.
(a) Absolute value command system
As position data, set the target address to be reached.
Setting range: -999999 to 999999 [×10
STM
μm] (STM = feed length multiplication parameter No. PE02)
Position data setting range
[ 10
STM
m]
-999999 999999
(b) Incremental value command system
As position data, set the travel distance from the current address to the target address.
Setting range: 0 to 999999 ×10
STM
μm] (STM = feed length multiplication parameter No. PE02)
Current address Target address
Position data = |target address - current address|