208
(5) Alert output signal assignment
Assign Alert output signal (RX18) of the main A/D converter module to Remote output (RY) of the extension
output module by using the external signal assignment function. When an alart is issued, assigned Remote
output (RY) is turned on.
(a) Setting range
With the head of Remote output (RY) of the main A/D converter module as a starting point (0000H), set the
number, which is counted from the head, of Remote output (RY) of the extension output module.
Ex.
When Alert output signal (RX18) is assigned to Remote output (RY) numbered 2H as counted from the
head (0H) of the extension output module
Remote output (RY) numbered 2H as counted from the head of the extension output module corresponds
to Remote output (RY) numbered 22H as counted from the head of the main A/D converter module.
Thus, set 22H for Alert output signal assignment (address: 0004H).
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is No assignment (FFFFH).
(d) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Setting a value out of the range results in the error code (0172H) being stored in Latest error code (RWr0), Error flag (RXA)
turning on, and the ERR. LED lighting up, with the previously set operation.
Remote buffer memory name Main A/D converter module Extension A/D converter module
Alert output signal assignment 0004H
0H to to1FH 20H to 22H 2FH
to0H to 2H FH
Main A/D converter module Extension output module