Appendix 3 Details of Remote Buffer Memory
(10)Digital output HOLD/CLEAR setting
Set the output HOLD/CLEAR of the extension output module.
For the output HOLD/CLEAR setting function, refer to the following:
CC-Link IE Field Network Remote I/O Module User's Manual
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is CLEAR (0H).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
● When no extension output module is connected, the setting of Digital output HOLD/CLEAR setting (address: 0011H) is
ignored.
● Setting data other than the above results in operation with the set value of the lower 1 bit.
(11)A/D conversion enable/disable setting
Set whether to enable or disable A/D conversion for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is Enabled (0) for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Output HOLD/CLEAR setting Setting value
CLEAR 0H
HOLD 1H
Remote buffer memory name Main A/D converter module Extension A/D converter module
Digital output HOLD/CLEAR setting 0011H
Remote buffer memory name
Main A/D converter module Extension A/D converter module
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4
A/D conversion enable/disable setting 0102H 0202H
00000000000 CH1CH2CH3CH40
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b0b1b2b3b4
0: A/D conversion enabled
1: A/D conversion disabled
The values of b4 to b15 are fixed to 0.