216
(14)CH Time average/Count average/Moving average
This area is used for setting the time average, count average, or moving average for each channel where the
averaging processing is specified.
The following shows the setting range.
*1 For time average, set a value of (4 × Sampling period) ms or more. A value less than this criterion results in the error
code (020H, 120H) being stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting
up. In CH Digital operation value (RWr2 to RWr5, RWr12 to RWr15), 0 is stored.
*2 Setting data other than the above results in the error code (030H and 130H, or 031H and 131H) being stored in
Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting up. The A/D conversion processing is
performed with the settings just before the error.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is 0 for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
By default, 0 is set and so change the value according to the processing method.
For the channel where any value is set up, setting the sampling processing results in the set value being ignored.
Processing method Setting value
Time average
*1
2 to 5000(ms)
Count average
*2
4 to 65000 (times)
Moving average
*2
2 to 128 (times)
Remote buffer memory name
Main A/D converter module Extension A/D converter module
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4
CH Time average/Count average/Moving
average
0105H 0106H 0107H 0108H 0205H 0206H 0207H 0208H