Appendix 3 Details of Remote Buffer Memory
(21)CH Maximum value, CH Minimum value
The maximum and minimum values of converted digital operation value are stored as signed 16-bit binary.
See below for reset.
Turning on and off Maximum value/minimum value reset request (RY1D) of the main A/D converter module
results in CH Maximum value and CH Minimum value of the main A/D converter module being updated
to the current value.
Turning on and off Maximum value/minimum value reset request (RY2D) of the extension A/D converter
module results in CH Maximum value and CH Minimum value of the extension A/D converter module
being updated to the current value.
Turning on and off Initial data setting request flag (RY9) results in CH Maximum value and CH Minimum
value of both the main A/D converter module and the extension A/D converter module being updated to the
current value.
(a) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
With the averaging processing specified, the maximum and minimum values are updated per averaging process cycle;
otherwise, updated per sampling cycle.
With the following functions used, values computed by each function are stored in the maximum value and the minimum
value:
Digital clipping function
Scaling function
Shift function
Difference conversion function
(22)Extension module identification code
The identification code for a connected extension module is stored.
If the extension A/D converter module is connected, 2111H is stored.
For the identification code for extension modules other than the extension A/D converter module, refer to the
following:
Manual including the description of the extension module used
(a) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Main A/D converter module Extension A/D converter module
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4
CH Maximum value 0601H 0603H 0605H 0607H 0701H 0703H 0705H 0707H
CH Minimum value 0602H 0604H 0606H 0608H 0702H 0704H 0706H 0708H
Remote buffer memory name Main A/D converter module Extension A/D converter module
Extension module identification code 0700H