223
APPX
A
Appendix 3 Details of Remote Buffer Memory
(b) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
(24)Error history clear command
This command is used to clear the error history stored in the non-volatile memory.
(a) Behavior of error history clear
Setting Error history clear command (address: 1000H) to Commanded (1) allows the error history to be
cleared.
(b) Default value
The default value is Not commanded (0).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name Main A/D converter module Extension A/D converter module
Error history data 0A00H to 0AEFH
Remote buffer memory name Main A/D converter module Extension A/D converter module
Error history clear command 1000H
The values of b1 to b15 are fixed to 0.
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
0000000000 0000 0
0: Not commanded
1: Commanded
Controlled by the A/D converter module
Contents of error history
Error history clear command
(address: 1000H)
Error history clear completed
(address: 1001H)
Controlled by the program
Error history stored Error history not stored
Not
commanded (0)
Not
commanded (0)
Commanded (1)
Not
performed (0)
Not performed (0)
Completed
(1)