33
CHAPTER 3 SPECIFICATIONS
3
3.5 List of Remote I/O Signals
3.5.1 Main A/D converter module
Do not use any "Use prohibited" remote I/O signals. If any of the signals are used, correct operation of the module cannot be
guaranteed.
Module type
Remote input Remote output
Signal direction: Main A/D converter module→Master/local
module
Signal direction: Master/local module→Main A/D converter
module
Device No. Description Device No. Description
Main A/D
converter module
RX0 Use prohibited RY0 Use prohibited
RX1 Use prohibited RY1 Use prohibited
RX2 Use prohibited RY2 Use prohibited
RX3 Use prohibited RY3 Use prohibited
RX4 Use prohibited RY4 Use prohibited
RX5 Use prohibited RY5 Use prohibited
RX6 Use prohibited RY6 Use prohibited
RX7 Warning flag RY7 Use prohibited
RX8 Use prohibited RY8 Use prohibited
RX9 Initial data setting completion flag RY9 Initial data setting request flag
RXA Error flag RYA Error clear request flag
RXB Remote READY RYB Use prohibited
RXC Use prohibited RYC Use prohibited
RXD Use prohibited RYD Use prohibited
RXE Use prohibited RYE Use prohibited
RXF Use prohibited RYF Use prohibited
RX10 CH1 A/D conversion completed flag RY10 Use prohibited
RX11 CH2 A/D conversion completed flag RY11 Use prohibited
RX12 CH3 A/D conversion completed flag RY12 Use prohibited
RX13 CH4 A/D conversion completed flag RY13 Use prohibited
RX14 CH1 Difference conversion state flag RY14 CH1 Difference conversion trigger
RX15 CH2 Difference conversion state flag RY15 CH2 Difference conversion trigger
RX16 CH3 Difference conversion state flag RY16 CH3 Difference conversion trigger
RX17 CH4 Difference conversion state flag RY17 CH4 Difference conversion trigger
RX18 Alert output signal RY18 Use prohibited
RX19 Trigger conversion completed flag RY19 Trigger conversion request
RX1A Use prohibited RY1A Trigger conversion completed clear request
RX1B Use prohibited RY1B Use prohibited
RX1C Input signal error detection signal RY1C Use prohibited
RX1D
Maximum value/minimum value reset
completed flag
RY1D Maximum value/minimum value reset request
RX1E Use prohibited RY1E Use prohibited
RX1F
External power supply monitor status flag (for
extension output module)
RY1F
External power supply monitor request flag
(for extension output module)