59
CHAPTER 6 INSTALLATION AND WIRING
6
6.4 Wiring to Terminal Block for Module Power Supply and FG
(4) Connecting and disconnecting a cable
To connect a cable, with the terminal screw loosened using a flathead screwdriver, insert the wire and then
tighten the terminal screw.
To disconnect the cable, with the terminal screw loosened using a flathead screwdriver, pull out the wire.
(5) Cable terminal processing
Strip the cable sheath approximately 10mm from the end.
To use a bar solderless terminal, connect it to the stripped part.
(6) List of bar solderless terminals
The following table lists recommended bar solderless terminals.
Product name Model Applicable wire size Contact
Bar solderless terminal
TE 0.5-10 0.5
NICHIFU Co., Ltd.
TE 0.75-10 0.75
TE 1.0-10 0.9 to 1.0
TE 1.5-10 1.25 to 1.5
Bar solderless terminal tool NH79
Bar solderless terminal
AI 0.5-10WH 0.5
Phoenix Contact Co., Ltd.
AI 0.75-10GY 0.75
AI 1-10RD 1.0
AI 1.5-10BK 1.5
Bar solderless terminal tool CRIMPFOX6
Cable
Approx. 10mm