154
7 PARAMETER SETTING
7.1 Network Configuration Setting
Setting item list
*1 For the RX/RY setting and the RWw/RWr setting, set a value in the corresponding setting range. If a value outside the setting range is
set, an error occurs on the network configuration setting window.
*2 For an I/O module that does not support the CC-Link IE TSN Network synchronous communication function, set "Asynchronous" for this
item. If "Synchronous" is set, an error (error code: D020H) occurs in the I/O module or the event code of 00C71 is registered with event
history of the master station.
For the firmware version of an I/O module that supports the CC-Link IE TSN Network synchronous communication function, refer to the
following.
Page 256 Added and Changed Functions
*3 The value depends on the input points or the output points of the I/O modules. For the input points or output points, refer to the following.
Page 22 Performance Specifications
Item Description Setting range
RX Setting, RY Setting Points Set the assignment of RX/RY points in units of 16 points. 0 to 32 (Default value: 32/16)
*1*3
Start The RX/RY start number is displayed.
End The RX/RY end number is displayed.
RWr Setting, RWw Setting Points Set the assignment of RWw/RWr points in units of 4 points. 0 to 144 (Default value: 4)
*1
Start The RWw/RWr start number is displayed.
End The RWw/RWr end number is displayed.
Network Synchronous Communication Set whether to use the CC-Link IE TSN Network synchronous
communication function.
*2
• Asynchronous (Default value)
• Synchronous
Communication cycle setting Set the cycle of the I/O module when setting multiple
communication cycles.
When the communication speed differs between the master
station and the I/O module, the setting range is limited. (
Page 151 Communication cycle interval setting)
• Basic cycle
• Medium speed
• Low speed