210
11 TROUBLESHOOTING
11.5 Examples of Troubles with the I/O Module
A load operates only by turning on the external power supply (transistor output)
Cause
The external power supply is connected with its polarity reversed.
The reversed polarity may allow current to flow via the output element protection diode into the load.
Action
Connect the external power supply with the correct polarity.
COM-
Y0
Load
External
power
supply
Incorrect Correct
Output element
protection diode
Sink output
COM+
Y0
Load
External
power
supply
Incorrect Correct
Output element
protection diode
Source output

Table of Contents