APPX
Appendix 2 Remote Register
243
A
Output Y OFF information clear request
Device number
Description
This remote register is used to clear Output Y OFF information Y (RWrE, RWrF). ( Page 176 Output OFF information)
Output Y OFF information clear request Y0 to YF (RWwE)
Output Y OFF information clear request Y10 to Y1F (RWwF)
Synchronization output timing setting
Device number
Description
When the synchronization cycle timing control mode is used, set the output timing relative to the synchronization cycle start
timing.
Set the timing to change the output from OFF to ON, or from ON to OFF in one synchronization cycle.
If the values set in Synchronization output timing setting Y OFF to ON (RWw10, RWw11, ... , RWw8C, RWw8D) and
Synchronization output timing setting Y ON to OFF (RWw12, RWw13, ... , RWw8E, RWw8F) are the same for one output,
the output does not change.
Setting value
Set the time (unit: ns) taken from the synchronization cycle start timing to the output change.
The following table lists the setting values.
Name Device number
Output Y OFF information clear request RWwE, RWwF
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
YF YE YD YC YB YA Y9 Y8 Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0
Off: Output Y OFF information is not cleared.
On: Output Y OFF information is cleared.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Y1F Y1E Y1D Y1C Y1B Y1A Y19 Y18 Y17 Y16 Y15 Y14 Y13 Y12 Y11 Y10
Off: Output Y OFF information is not cleared.
On: Output Y OFF information is cleared.
Name Device number
Synchronization output timing setting Y RWw10 to RWw8F
Setting value Description
0 to 4294967294 (00000000H to FFFFFFFEH) The output changes at preset timing.
4294967295 (FFFFFFFFH) The output does not change.