3 SPECIFICATIONS
3.3 Performance Specifications
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF ON, and 160s at ON OFF.
*2 Make sure that the total amount of output current that flows through one connector is 4A or less.
*3 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 228 I/O combined module
(16-point module))
*4 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
Derating chart
Weight 0.42kg
: Module-and-sensor power supply current, 8A
: Module-and-sensor power supply current, 6A
The module-and-sensor power supply current is 6A when the ambient temperature is 40 or higher.
Item NZ2GN12A42-16DT
12
8
04055
0
Ambient temperature ()
Max. load current
(common)
(A/common)
12A/common at 40
8A/common at 55