9 PROGRAMMING
9.2 Program Example
187
9
Setting procedure
Operating procedure
1. Create a project.
[Project] [New...]
2. For "CPU Parameter" in "Link Direct Device Setting", set "Extended Mode (iQ-R Series Mode)".
[CPU Parameter] [Memory/Device Setting] [Link Direct Device Setting] [Link Direct Device Setting]
When writing the module parameters of the RJ71GN11-T2 to the CPU module with the engineering tool, set
"Extended Mode (iQ-R Series Mode)" for "Link Direct Device Setting".
When "Q Series Compatible Mode" is set for "Link Direct Device Setting", "Write to PLC" cannot be executed.
3. Set the master/local module in the following window.
[Navigation window] [Parameter] [Module Information] Right-click [Add New Module]