APPX
Appendix 2 Remote Register
237
A
Output Y OFF information
Device number
Description
Whether output Y has been turned off or not can be checked with Output Y OFF information Y (RWrE, RWrF).
When the synchronization output timing setting control or the output time setting control (CC-Link IE TSN
Network synchronous communication function) is used, whether output Y has been turned off or not can be
checked with Output Y OFF information Y (RWrE, RWrF).
Output Y OFF information Y0 to YF (RWrE)
Output Y OFF information Y10 to Y1F (RWrF)
Output Y OFF information Y (RWrE, RWrF) can be cleared using Output Y OFF information clear request Y (RWwE,
RWwF).
While Output Y OFF information clear request is turned on, regardless of the remote output signal status,
output Y OFF information continues to be cleared.
Name Device number
Output Y OFF information RWrE, RWrF
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
YF YE YD YC YB YA Y9 Y8 Y7 Y6 Y5 Y4 Y3 Y2 Y1 Y0
Off: Output Y has never been turned off.
On: Output Y has been turned off.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Y1F Y1E Y1D Y1C Y1B Y1A Y19 Y18 Y17 Y16 Y15 Y14 Y13 Y12 Y11 Y10
Off: Output Y has never been turned off.
On: Output Y has been turned off.
Performed by I/O module
Executed by the program
(1) Remains on even after Y0 turns on.
(2) Turns off when the clear request turns on.
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
(2)
OFF
ON
ON
OFFOFF
OFF
OFF
(1)
External output signal Y0
Output Y current value Y0
(RWrA. b0)
Output Y OFF information Y0
(RWrE.b0)
Output Y OFF information
clear request Y0 (RWwE.b0)
Remote output signal RY0