EasyManua.ls Logo

Mitsubishi Electric Q02CPU-A - Page 48

Mitsubishi Electric Q02CPU-A
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 - 2
CPU MODULE4.
Performance specifications (continued)
Item
Model
Remark
Q02CPU-A Q02HCPU-A Q06HCPU-A
Device points
Internal relay [M] 7144 points (M0 to M999, M2048 to M8191)
Total 8192 shared by
M, L, S
The range can be
changed by
parameters.
Latch relay [L] 1048 points (L1000 to L2047)
Step relay [S] 0 point (None for default)
Link relay [B] 8192 points (B0 to B1FFF)
Timer [T]
2048 points (Default: 256 points)
•100ms timer (T0 to T199) ...................... Setting time: 0.1 to 3276.7s
•10ms timer (T200 to T255) ................... Setting time: 0.01 to 327.67s
•100ms retentive timer (none for initial) .... Setting time: 0.1 to 3276.7s
•Expansion timer (T256 to T2047) ........ Time set by word device (D, W, R)
•1ms timer (None for initial).......
The range and number
of points for use set by
parameters
(Refer to Section 4.2.1)
Counter [C]
1024 points (Default: 256 points)
•Normal counter (C0 to C255) .............. Setting range : 1 to 32767 times
•Interrupt counter (none for default)
............C224 to C255 possible depending on setting
•Expansion counter (C256 to C1023)
.................. Count value set by word device (D,W,R)
The range and number
of points for use set by
parameters
(Refer to Section 4.2.1)
Data register [D] 8192 points (D0 to D8191)
Link register [W] 8192 points (W0 to W1FFF)
Annunciator [F] 2048 points (F0 to F2047) Fault finding device
File register [R] 8192 points (R0 to R8191)
Points set by
parameters
Accumulator [A] 2 points (A0, A1)
Index register [V, Z] 14 points (V, V1 to V6, Z, Z1 to Z6)
Pointer [P] 256 points (P0 to P255)
Interrupt pointer [I] 32 points (I0 to I31)
Special relay [M] 256 points (M9000 to M9255)
Special register [D] 256 points (D9000 to D9255)
Setting time: 0.001 to 32.767s (The latter
half of the retentive timer can be used by
ZHTIME instruction.)

Table of Contents