CHAPTER 4 INSTALLATION AND WIRING
4
4.8 Wiring
4.8.2 Wiring of 18-point screw terminal block
4.8.2 Wiring of 18-point screw terminal block
(1) Precautions
Insulation-sleeved crimping terminals cannot be used with the terminal block.
It is recommended to cover the wire connections of the crimping terminals with mark or insulation tubes.
The wires used for connection to the terminal block must be 0.3 to 0.75mm
2
in core and 2.8mm max. in
outside diameter.
Run the input and output lines away from each other.
When the lines cannot be run away from the main circuit and power lines, use a batch-shielded cable and
ground it on the programmable controller side.
In some cases, ground it in the opposite side.
Where wiring runs through piping, ground the piping.
Run the 24VDC input line away from the 100VAC and 200VAC lines.
Wiring of 200m or longer will raises current leakage due to the line capacity, resulting in a fault.
To prevent electric shock or malfunction, provide the external power supply for the module to be changed
online with means that can turn the power supply off individually, e.g. a switch. ( Page 265, CHAPTER
14)
As a countermeasure against the power surge due to lightning, separate the AC wiring and DC wiring and
connect a surge absorber for lightning as shown in Page 103, Section 4.8.1.
Failure to do so increases the risk of I/O device failure due to lightning.
For screw terminal blocks other than the 18-point screw terminal block, refer to the user's manual for the module used.
DC
RA
Programmable
controller
Shield cable
Input
Output
Shield jacket