CHAPTER 5 GENERAL SPECIFICATIONS
5
CHAPTER 5 GENERAL SPECIFICATIONS
The following table lists the general specifications of the programmable controller.
*1 This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand
level for up to the rated voltage of 300V is 2500V.
*2 This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be
expected occasionally.
*3 The storage ambient temperature is -20 to 75°C if the system includes the AnS/A series modules.
*4 The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system includes the AnS/A series
modules.
*5 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local
Mitsubishi Electric representative.
Item Specifications
Operating ambient
temperature
0 to 55°C
Storage ambient
temperature
-25 to 75°C
*3
Operating ambient
humidity
5 to 95%RH
*4
, non-condensing
Storage ambient
humidity
Vibration resistance
Compliant with
JIS B 3502 and
IEC 61131-2
Frequency
Constant
acceleration
Half amplitude Sweep count
Under
intermittent
vibration
5 to 8.4Hz ---- 3.5mm
10 times each in
X, Y, Z directions
8.4 to 150Hz
9.8m/s
2
----
Under continuous
vibration
5 to 8.4Hz ---- 1.75mm
----
8.4 to 150Hz
4.9m/s
2
----
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147 m/s
2
, 3 times each in 3 directions X, Y, Z)
Operating
atmosphere
No corrosive gases
Operating altitude
*5
0 to 2000m
Installation location Inside a control panel
Overvoltage
category
*1
II or less
Pollution degree
*2
2 or less
Equipment class Class I