373
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.5 List of error codes (3000 to 3999)
3400
[REMOTE PASS. ERR.]
The start I/O number of the remote password
target module is set to other than 0
H
to 0FF0
H
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Set the start I/O number within the range, 0
H
to 0FF0
H
.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
[REMOTE PASS. ERR.]
The start I/O number of the remote password
target module is set to other than 0
H
to 07E0
H
.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Set the start I/O number within the range, 0
H
to 07E0
H
.
Q02UCPU
[REMOTE PASS. ERR.]
The start I/O number of the remote password
target module is not in the following range.
• Q00JCPU: 0
H
to 1E0
H
• Q00CPU/Q01CPU: 0
H
to 3E0
H
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Set the start I/O number within the following
range.
• Q00JCPU: 0
H
to 1E0
H
• Q00CPU/Q01CPU: 0
H
to 3E0
H
Q00J/Q00/Q01
[REMOTE PASS. ERR.]
The start I/O number of the remote password
target module is out of range.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Correct the start I/O number. LCPU
3401
[REMOTE PASS. ERR.]
There is a problem in the slot specified by the start
I/O number of the remote password target module:
• No module is mounted.
• A module (such as I/O module) other than
intelligent function modules is mounted.
• An intelligent function module other than a serial
communication module or Ethernet module is
mounted.
• The function version of a serial communication
module or Ethernet module mounted is A.
• An intelligent function module that does not
support the use of remote password is mounted.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Mount the following modules in the slot
specified by the start I/O number of the
remote password target module.
• Serial communication module whose
function version B or later
• Ethernet module whose function version B
or later
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
QnU
[REMOTE PASS. ERR.]
There is a problem in the slot specified by the start
I/O number of the remote password target module:
• No module is mounted.
• An intelligent function module other than a serial
communication module or Ethernet module is
mounted.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
Mount an intelligent function module that
supports the use of remote password in the
specified slot.
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU