EasyManua.ls Logo

Mitsubishi Electric Q06HCPU - Appendix 1.9 List of Error Codes (7000 to 10000)

Mitsubishi Electric Q06HCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
402
Appendix 1.9 List of error codes (7000 to 10000)
The following table shows the error messages, the error contents and causes, and the corrective actions for the error
codes (7000 to 10000).
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU
7000
[MULTI CPU DOWN]
In the operating mode of a multiple CPU
system, a CPU error occurred at the CPU where
"All station stop by stop error of CPU " was
selected.
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system was
mounted.
Any CPU module other than CPU No.1 was
disconnected from the base unit during
operation. Or any CPU module other than CPU
No.1 was reset.
At power-on/reset, momentary power failure has
occurred.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
Always
Read the common information of the error
using the programming tool. Check the
error in the CPU module, and eliminate the
error cause.
Remove the CPU module from the main
base unit if it does not support the multiple
CPU system configuration.
Check the mounting status of CPU
modules other than CPU No.1 and whether
the CPU modules were reset.
Check the power supply.
The cause is a hardware failure of the
power supply module. Please consult your
local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
[MULTI CPU DOWN]
In a multiple CPU system, CPU other than CPU
No.1 cannot be started up due to stop error of the
CPU No.1 at power-on, which occurs to CPU No.2
to No.4.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Read the common information of the error
using the programming tool. Check the error
in the CPU module, and eliminate the error
cause.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
7002
[MULTI CPU DOWN]
There is no response from the target CPU
module in a multiple CPU system during initial
communication.
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system was
mounted.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of any of the
CPU modules. Please consult your local
Mitsubishi representative.
Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
[MULTI CPU DOWN]
There is no response from the target CPU module
in a multiple CPU system during initial
communication.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reset t
he CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of any of the CPU
modules. Please consult your local Mitsubishi
representative.
QnU
7003
[MULTI CPU DOWN]
There is no response from the target CPU module
in a multiple CPU system at initial communication
stage.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of any of the CPU
modules. Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU

Table of Contents