Appendix 8.1.1 Standards relevant to the EMC Directive
(1) Regulations regarding emission
*1 QP: Quasi-peak value, Mean: Average value
*2 Programmable controllers are open-type devices (devices designed to be housed inside other equipment) and must be
installed inside a conductive control panel. The corresponding tests were conducted with the programmable controller
installed inside a control panel.
Standard Test item Test description Value specified in standard
EN61131-2:
2007
CISPR16-2-3
Radiated emission
*2
Radio waves from
the product are
measured.
30M-230MHz
QP: 40dB µ V/m (10m in
measurement range)
*1
230M-1000MHz
QP: 47dB µ V/m (10m in
measurement range)
CISPR16-2-1,
CISPR16-1-2
Conducted emission
*2
Noise from the product to the
power line is measured.
150k-500kHz
QP: 79dB, Mean: 66dB
*1
500k-30MHz
QP: 73dB, Mean: 60dB

Table of Contents