FUNCTIONS
4.3 Remote Operation Function
4.3.3 Remote RESET
4 - 12
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
(4) Remote RESET timing
The remote RESET is executable in the STOP status only. When the C Controller
module or programmable controller CPU is in the RUN status, change the status to
STOP by remote STOP.
Even if the RUN/STOP/MODE, RUN/STOP, or RUN/STOP/RESET switch of the C
Controller module or programmable controller CPU is set to RUN, it can be reset
when it is stopped due to an error that can be detected by the self-diagnostic function.
(5) Confirmation before remote RESET
(a) When the C Controller module is used in a single CPU system, or is CPU No.1 in
a multiple CPU system
Check the following conditions 1) and 2) before executing remote RESET.
Remote RESET is not available if either of 1) and 2) is not satisfied.
1) Setting required for remote RESET
In <<System settings>> of C Controller setting utility, the "Allow" box must be
checked for "Remote reset", and parameters must have already been written
to the C Controller module. (Write the parameters and then reset the C
Controller module.)
2) C Controller module status
The C Controller module should be in the STOP status.
Figure 4.4 Setting remote reset to Allow
Set to "Allow".