4 - 25
4.5 Self-Diagnostic Function
4
FUNCTIONS
(5) Clearing errors
A C Controller module can clear only continuation errors.
The errors cannot be cleared with the following C Controller modules.
Q12DCCPU-V with a serial number whose first five digits are "12041" or higher
Q06CCPU-V(-B)
(a) Error clear procedure
To clear errors, complete the following procedure.
1) Eliminate the reason for the error.
2) Perform one of the following operations or processes.
Click the button on the <<Module information>> tab of the
C Controller setting utility.
Execute the QBF_ClearError function.
3) The target error will be cleared.
(b) The status after clearing errors
When the C Controller module is restored with error clear, the special relay,
special register and LED related to the error return to the status before the
error occurred.
When the same error occurs after error clear is performed, the error is
registered to the event history again.
POINT
Errors
(*1)
occurring as a result of cause other than the C Controller module
cannot be cleared until the cause of the error is eliminated, even if the error clear
operation or processing is performed.
* 1 "SP.UNIT DOWN", etc.
For eliminating of error causes, refer to the following.
Page 16-1, CHAPTER 16
Error clear