5 - 2
5.2 CC-Link Module Access Function
5
ACCESS VIA NETWORK MODULES
5.2 CC-Link Module Access Function
(1) The CC-Link module access function
This function allows access to each station, programmable controller CPU on another
station, or C Controller module that is connected to CC-Link via CC-Link modules.
In a multiple CPU system, access cannot be made via a CC-Link module controlled
by another CPU.
To create user programs of the C Controller module, use MELSEC data link functions
or bus interface functions.
For the Q06CCPU-V-B, MELSEC data link functions cannot be used.
When the Q06CCPU-V-B is used, use cyclic transmission for access to a CPU
module on another station.
Remark
For the bus interface functions and MELSEC data link functions, refer to the
following.
C Controller Module User's Manual (Utility Operation, Programming)
Figure 5.1 Access via CC-Link
Q12DCCPU-V
Q06CCPU-V
Q06CCPU-V-B
COM-COM+COM-COM+ COM+ COM+ COM+ COM+ DC24G
DC24VYBYAY9Y8X3X2X1X0
4020108421421
B RATESTATION NO.
ON
PW L RUN L ERR X0 1 2 3 Y8 9 A B
A
J65SBTB32-8DT2
DA DG +24V 24G
DB SLD (FG)
MITSUBISHI
ret = mdSend(path, stno, devtyp, devno, size, data);
ret = QBF_ToBuf(path, iono, offset, size, data, datasize);
<Example>
C Controller module
/* Reads device data of the other station programmable controller CPU */
ret = mdReceive(path, stno, devtyp, devno, size, data);
/* Writes data to its own station RY and outputs it to the remote I/O module */
or
2)
1)
C Controller module
CC-Link master station
Access via CC-Link
Remote I/O station
Local station
Programmable
controller CPU
Device data
1) Reads the device data of the other station programmable
controller CPU to the C Controller module via the CC-
Link module.
2) Writes data to RY of the CC-Link module itself and outputs
it to the remote I/O module.

Table of Contents