6
PREPARATORY PROCEDURES AND SETTING
6.7 Specifications, Installation, and Replacement of the Battery
6.7.3 Battery replacement
6 - 49
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
6.7.3 Battery replacement
This section explains the replacement of the C Controller module battery.
The C Controller module battery is used for the following purposes.
• Backup of the standard RAM files
• Protection of the standard ROM files
• Backup of the battery-backed-up RAM data
• Backup of the clock data
The battery must be replaced when the battery voltage becomes low.
(1) Checking for low battery voltage of the C Controller module
(a) Setting for low battery voltage detection
1) In the <<System settings>> tab of C Controller utility, select "Battery check" in
the Error check area.
2) Click the button in the <<Online operation>> tab of C Controller utility to
write the parameters to the C Controller module.
3) Reset the C Controller module by the RESET/SELECT switch on the module.
(In the case of a multiple CPU system, reset CPU No.1.)
A battery error can be detected by the above procedure 1) to 3).
Figure 6.43 Setting for low battery voltage detection
Q06CCPU-V-B