6
PREPARATORY PROCEDURES AND SETTING
6.10 Initializing/Changing Mode of C Controller Module
6.10.1 Initializing/Changing mode of Q12DCCPU-V
6 - 75
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
(5) Default IP setting mode
To set the IP address back to default, start the C Controller module in the hardware
self-diagnostic mode ( Page 16-75, Section 16.5.1), and then execute the
"Default IP setting" mode.
1) Start up the C Controller module in the hardware self-diagnostic mode (with
the RUN/STOP/MODE switch set to MODE).
(The MODE LED turns on in orange.)
2) Repeatedly move the RESET/SELECT switch to SELECT until the 7-segment
LED indicates "10".
Check that the 7-segment LED is indicating "10" and the current mode is
"Default IP setting".
3) Set the RUN/STOP/MODE switch to RUN to execute the "Default IP setting"
mode.
(The RUN LED starts flashing.)
When the "Default IP setting" mode is activated:
• The RUN LED turns off.
• The 7-segment LED indicates "00".
4) In the "Default IP setting" mode, reset or restart the C Controller module.
After resetting or restarting the C Controller module, the module will be in the
following status:
• Default IP address of CH1: 192.168.3.3
Default IP address of CH2: No setting
• Script file: None
5) Access the C Controller module from C Controller setting utility using the
default IP address of CH1 (192.168.3.3) and write default parameters.
Before writing parameters, open the <<Online operation>> tab and select
"Clear all parameter before writing" in the "Write parameters" area.
Resetting or restarting the C Controller module sets the module into the
initialized status.