7
I/O NUMBER ASSIGNMENT
7.6 I/O Assignment by C Controller Setting Utility
7.6.2 Details of I/O assignment by C Controller setting utility
7 - 20
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
(b) Type (C Controller module uses this setting.)
Select the type of each module from the following.
Empty (Empty slot)
Input (Input module)
Hi Input (High-speed input module)
Output (Output module)
I/O Mix (I/O combined module)
Intelli. (Intelligent function module)
Interrupt (Interrupt module)
If no type is specified, the type of the actually mounted module is used for the slot.
(c) Model name
Enter the module model name within 16 characters.
The C Controller module does not recognize this setting. (Use this setting as a
note.)
(d) Points (C Controller module uses this setting.)
To change the number of I/O points for each slot, select one from the following.
• 0 (0 points) • 16 (16 points) • 32 (32 points)
• 48 (48 points) • 64 (64 points) • 128 (128 points)
• 256 (256 points) • 512 (512 points) • 1024 (1024 points)
To the slot with no point setting, the points of the actually mounted module is
assigned.
(e) Start X/Y (C Controller module uses this setting.)
When changing I/O numbers of each slot, enter a new start I/O number.
To the slot with no start X/Y setting, I/O numbers following those of the configured
slot are assigned in order.