12.4 Access Ranges Between a CPU Module and Other Modules
12.4.2 Access to non-controlled modules
12
CONCEPT OF MULTIPLE CPU SYSTEM
(1) Input (X) loading
Whether to load inputs from input modules and intelligent function modules controlled
by other CPUs is determined by the "I/O sharing when using Multiple CPUs"
parameter in the <<Multiple CPU settings>> tab of C Controller setting utility.
(a) When "All CPU s can read all inputs" is selected
1) On/off data are loaded from input modules or intelligent function modules
controlled by other CPUs to the input (X) of the host CPU by execution of a bus
interface function.
Figure 12.7 I/O sharing when using multiple CPUs (Input loading)
Figure 12.8 When CPU No.1 loads inputs
I/O sharing when using Multiple CPUs
All CPUs can read all inputs:
"All CPUs can read all inputs" has been set
All CPUs can read all inputs:
"Not all CPUs can read all inputs" has been set
2
2 Control CPU setting2
Read when bus interface function
is executed.
Slot number
CPU 0 1 2 3 4
/* X is read in 1 word unit */
ret = QBF_X_In_WordEx(path, flg, xno, size, data, datasize);
Input module
Output module
Input module
Output module