12 - 18
12.4 Access Ranges Between a CPU Module and Other Modules
12.4.2 Access to non-controlled modules
12
CONCEPT OF MULTIPLE CPU SYSTEM
(3) Output to output modules and intelligent function modules
On/off data cannot be output to non-controlled modules.
Even if turning on or off the output of an output module or intelligent function module
controlled by another CPU is attempted from a C Controller module, no output is
made to the output module or intelligent function module.
(4) Access to the buffer memory of an intelligent function module
(a) Reading from the buffer memory
Buffer memory data of intelligent function modules controlled by other CPUs can
be read by using a bus interface function (QBF_FromBuf).
Figure 12.12 When CPU No.1 outputs data to modules
Figure 12.13 Reading from intelligent function modules
2
2 Control CPU setting2
Cannot turn ON/OFF.
Can turn ON/OFF when
bus interface function is
executed.
Slot number
CPU 0 1 2 3 4
/* Y is output in 1 word unit */
ret = QBF_Y_Out_WordEx(path, flg, yno, size, data, datasize);
Input module
Output module
Input module
Output module
1 1 1 1 1
2 222
Read when bus interface function
is executed.
Control CPU setting
Slot number
Intelligent function modules
CPU 0 1 2 3 4 5 6 7