16.2.5 When UNIT VERIFY ERR. occurred
Figure 16.4 When UNIT VERIFY ERR. occurred
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Check the error information in
<<Module information>> or
<<Event history>> of C Controller
setting utility.
Was the module on
the relevant slot removed and
remounted during
operation?
It is a hardware fault.
Consult your local Mitsubishi service
center or representative, explaining the
details of the problem.
Is the module
on the slot mounted
properly?
UNIT VERIFY ERR. occurred
Are all the
extension cables of
the base unit connected
properly?
Was the error
removed?
Was the error
removed?
Mount the module properly.
Connect the extension cables properly.
Was the error
removed?
Replace the relevant module.
End
Reset the C Controller module.
Has any error occurred?
Has any error occurred?
Has any error occurred?
No
No
No
Replace the relevant module.
Replace the C Controller module.
Replace the relevant base unit.
Yes
Yes
Yes