16.5 Hardware Self-Diagnostic Function
16.5.1 Hardware self-diagnostic test and initialization setting of the Q12DCCPU-V
16 - 82
9
DEVICE DESCRIPTION
10
MULTIPLE CPU SYSTEM
OVERVIEW
11
MULTIPLE CPU SYSTEM
CONFIGURATION
12
CONCEPT OF MULTIPLE
CPU SYSTEM
13
COMMUNICATIONS
BETWEEN CPU
MODULES
14
PARAMETERS ADDED
FOR MULTIPLE CPU
SYSTEMS
15
STARTING A MULTIPLE
CPU SYSTEM
16
TROUBLESHOOTING
* 1 An error may occur if an Ethernet cable (crossing cable) is not connected properly.
Correctly connect and wire the cable again, and then reexecute the self-diagnostic test for Mode 2.
* 2 An error may occur if a CompactFlash card is not inserted.
Insert a CompactFlash card and then reexecute the self-diagnostic test for Mode 3.
* 3 An error may occur if a self-loopback distribution cable is not connected correctly.
Correctly connect and distribute the cable again, and then reexecute the self-diagnostic test for
Mode 4.
Retry the diagnostics and setting if they failed.
If failure is detected again, the hardware of the C Controller module may be faulty.
Please consult your local Mitsubishi representative, explaining the details of the
problem.
Table 16.15 LED indication for error completion (error detection)
Mode Error detection 7-segment LED indication
Mode 1
During ROM diagnostic test
During work RAM diagnostic test
During battery-backed-up RAM
diagnostic test
Mode 2
During Ethernet(CH1) diagnostic
test
*1
During Ethernet(CH2) diagnostic
test
*1
During Ethernet loopback test
*1
Mode 3
During CompactFlash card interface
diagnostic test
*2
Mode 4
During RS-232 diagnostic test
*3
Mode 5 During USB diagnostic test
Mode 6 During bus diagnostic test
Default IP setting During setting the default IP
Module
initialization
setting
During initializing the module setting