2 - 10
2.1 System Configuration
2.1.4 System configuration overview
2
SYSTEM CONFIGURATION
Precautions
The total extension cable length must be 13.2m (43.31 feet) or less.
Do not install extension cables together with the main circuit lines (high
voltage and large current).
Set a unique number for each extension base.
The Q6 RB and QA1S6 B extension base units cannot be used.
Connect an extension cable from OUT of the extension cable connector of
the base unit to IN of the next extension base unit.
Mounting 65 or more modules causes an error.
Table 2.1 Restrictions on the system configuration
Maximum number of
extension base units
7 units
Maximum number of I/O
modules
64 modules
Main base unit model Q33B, Q35B, Q38B, Q312B
Extension base unit
model
No power supply module required Q52B, Q55B
Q series power supply module required Q63B, Q65B, Q68B, Q612B
Extension cable model QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q series power supply
module model
Q61P-A1, Q61P-A2, Q61P, Q61P-D, Q62P, Q63P, Q64P, Q64PN