2.2 Applicable Modules
2.2.2 Precautions for using I/O modules and intelligent function modules
2
SYSTEM CONFIGURATION
(3) Precautions for using a MELSECNET/H module
The following restrictions are applied to the MELSECNET/H module controlled by the
C Controller module.
The MELSECNET/H module cannot be used on a remote I/O network.
Use of the module is allowed on a PLC-to-PLC network only.
The module cannot be used as a relay station for the data link transfer function or
the routing function.
When using either of these functions, use a MELSECNET/H module controlled
by a programmable controller CPU as a relay station.
In a multiple CPU system, the host CPU (C Controller module) cannot
communicate via the MELSECNET/H module controlled by another CPU.
Another CPU also cannot communicate via the MELSECNET/H module
controlled by the host CPU.
The above is applied to the following communications.
Communications with MELSOFT connection
Communications using dedicated instructions
Communications using intelligent function modules
The link dedicated instructions for MELSECNET/H cannot be used.
Note that the message communication function equivalent to the SEND and
RECV instructions are available. ( Page 5-10, Section 5.3)
Interrupt sequence program start is not applicable.
The network diagnostics (test) function is not available.
The simple dual-structure network function is not applicable.
(The network type cannot be set to "MNET/H standby station")
When accessing to a redundant CPU on another station, the system of the
redundant CPU cannot be specified. Only host system access (station-number-
specified access) is available.
The mode cannot be set to "Debug mode".
The MELSEC data link functions cannot be used for the Q06CCPU-V-B.
For how to access a CPU module on another station when using the Q06CCPU-
V-B, refer to the following.
Page 5-10, Section 5.3