SYSTEM CONFIGURATION
2.2 Applicable Modules
2.2.2 Precautions for using I/O modules and intelligent function modules
2 - 21
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
(4) Precautions for using a CC-Link IE controller network module
The following restrictions are applied to the CC-Link IE controller network module
controlled by the C Controller module.
The module cannot be used as a relay station for the data link transfer function or
the routing function.
When using either of these functions, use a CC-Link IE controller network module
controlled by a programmable controller CPU as a relay station.
In a multiple CPU system, the host CPU (C Controller module) cannot
communicate via the CC-Link IE Controller Network module controlled by another
CPU. Another CPU also cannot communicate via the CC-Link IE Controller
Network module controlled by the host CPU.
The above is applied to the following communications.
Communications with MELSOFT connection
Communications using dedicated instructions
Communications using intelligent function modules
The link dedicated instructions for the CC-Link IE controller network cannot be
used.
Note that the message communication function equivalent to the SEND and
RECV instructions are available. ( Page 5-38, Section 5.4)
Interrupt sequence program start is not applicable.
When accessing to a redundant CPU on another station, the system of the
redundant CPU cannot be specified. Only host system access (station-number-
specified access) is available.
The group cyclic transmission function is not applicable.
The pairing setting for the redundant system is not applicable.
For the Q06CCPU-V-B, CC-Link IE controller network modules cannot be used.