2 - 22
2.2 Applicable Modules
2.2.2 Precautions for using I/O modules and intelligent function modules
2
SYSTEM CONFIGURATION
(5) Precautions for using the CC-Link IE field network master/local module
The following restrictions are applied to the CC-Link IE field network master/local
module controlled by the C Controller module.
(a) There are some unsupported functions.
For the unsupported functions, refer to the following.
MELSEC-Q CC-Link IE Field Network Master/Local Module User's Manual
(b) There is no module configuration/monitoring tool for the CC-Link IE field network
master/local module.
To configure parameters, write them to the buffer memory of the CC-Link IE
field network master/local module.
For the parameter setting method, refer to the following.
MELSEC-Q CC-Link IE Field Network Master/Local Module User's
Manual
For troubleshooting of the CC IE field network master/local module, use
either of the following methods.
If the C Controller module is connected to a CC-Link IE field network
master/local module that is mounted with a programmable controller CPU,
troubleshoot the problem from the CC-Link IE field network diagnostics in
GX Works2.
Check the error code in the buffer memory, link special relay (SB), and link
special register (SW) of the CC-Link IE field network master/local module.
For the CC-Link IE field network diagnostics, error codes, link special relays
(SB), and link special registers (SW), refer to the following.
MELSEC-Q CC-Link IE Field Network Master/Local Module User's
Manual
(6) Precautions for using a serial communication module
The serial communication module controlled by the C Controller module supports
nonprocedural protocol communications only.
(a) The following are not supported.
MC protocol and bidirectional protocol
The instructions dedicated to serial communication modules
The programmable controller CPU monitoring function
The modem function
(b) The following settings are required for using an interrupt program.
Set the interrupt event No. in the <<System settings>> tab of C Controller
setting utility.
Write "1" to the buffer memory (address 2010
H/2110H) of the serial
communication module.
Modify the user program so that an interrupt event will be received by the
QBF_WaitUnitEvent function to start relevant processing.