2 - 26
2.4 Applicable Devices
2
SYSTEM CONFIGURATION
(2) Twisted pair cable
Use the twisted pair cables that meet IEEE802.3 10BASE-T/100BASE-TX standards.
(a) At 100Mbps
Use either of the following cables.
Unshielded twisted pair (UTP) cable
Straight cable: Category 5 or higher
Crossing cable: Category 5 or 5e
Shielded twisted pair (STP) cable
Straight cable: Category 5 or higher
Crossing cable: Category 5 or 5e
(b) At 10Mbps
Use either of the following cables.
Unshielded twisted pair (UTP) cable
Straight cable: Category 3 or higher
Crossing cable: Category 3 to 5e
Shielded twisted pair (STP) cable
Straight cable: Category 3 or higher
Crossing cable: Category 3 or 5e
POINT
In the high-speed communication (100Mbps) by 100BASE-TX connection, a
communication error may occur due to high frequency noise generated from a
device other than the C Controller module, depending on the installation
environment.
When configuring a network system, take the following measures on the C
Controller module side to eliminate the influence of high frequency noise.
1. Wiring
Do not install the twisted pair cables together with the main circuit lines or
power cables.
Place the twisted pair cables in a duct.
2. Cable
In an environment where the system is susceptible to noise, use shielded
twisted pair (STP) cables.
3. Retry processing
In an environment where the system is susceptible to noise, include the
retry processing in the user program.
4. 10Mbps communication
Replace the devices connected to the C Controller module with 10Mbps
devices for communication at a speed of 10Mbps.