7 - 7
7 EMC DIRECTIVES
(3) Cable clamp
It is also possible to ground the exposed shielded part of the cable to the panel
with the AD75CK cable clamp (Mitsubishi).
• Ground the shield at a position 20 to 30cm (7.87 to 11.81 inch) away from the
module.
• When the cables pulled out from the control panel, ground the cables at a
position 5 to 10cm (1.97 to 3.94inch) near the input/output hole of the control
panel with the cable clamp (AD75CK), etc.
AD75CK
AD75CK
Inside control panel
Motion controller
5 to 10cm
(1.97 to 3.94 inch)
20 to 30cm
(7.87 to 11.81 inch)
• Cable clamp (Recommended product)
Manufacturer Model name
Mitsubishi electric
AERSBAN-DSET
AERSBAN-ESET
AD75CK
CAUTION
Do not ground the cable clamp to the top of control panel.
Doing so may lead to damage by drop of screws, etc. during installation or removing the cable clamp.