EasyManua.ls Logo

Mitsubishi Electric Q172CPU - Page 250

Mitsubishi Electric Q172CPU
634 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 - 21
6 PARAMETERS FOR POSITIONING CONTROL
6.3.14 Optional function 2
(1) Selection of no-motor operation
0: Invalid
1: Valid
If no-motor operation is valid, the output signals that would be output if the motor
were actually running can be output and statuses indicated without connecting a
servomotor.
It can be checked the Motion program of the Multiple CPU system without
connecting a motor.
(2) Electromagnetic brake interlock output timing
Select the output timing for the electromagnetic brake interlock signal from the
following.
0: It is output with any of the following conditions, regardless of the
rotational speed of the servomotor.
• Servo OFF
• Servo alarm occurrence
• Emergency stop input
1: It is output with the above conditions and the servo motor rotational
speed is "0 speed or less" of the expansion parameter.
(3) Slight vibration suppression function selection
(MR-J2S- B/MR-J2- B only)
Set to suppress vibration specific to the servo amplifier at the stop.
0: Slight vibration suppression control is invalid
1: Slight vibration suppression control is valid
(4) Motor lock function operation selection
(MR-J2S-
B/MR-J2- B only)
Allows test operation with the motor connected but without rotating the motor.
The operation is the same as no-motor operation with MR-H
BN.
0: Motor lock operation is invalid
1: Motor lock operation is valid
When motor lock operation is made valid, operation is possible without
connecting the motor. However, since when MR-J2S-
B/MR-J2- B is used the
connected motor is automatically identified before operation is started, if no motor
is connected the connected motor type may be regarded as a default, depending
on the type of amplifier. If this default motor type differs from the setting made in
the system settings, the controller will detect minor error [900] (motor type in
system settings differs from actually mounted motor), but this will not interfere
with operation.

Table of Contents

Other manuals for Mitsubishi Electric Q172CPU

Related product manuals