7 - 9 7 - 9
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.2 When industrial shipment setting is used and initial setting was made with sequence
program
(1) Conversion disable
(a) Take the following steps to disable the conversion:
1) Set D/A conversion enable/disable (buffer memory address 0: Un\G0)
to All channel conversion disable (F
H
).
2) Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3) Operating condition setting completed flag (X9) turns off from on.
4) Check that the conversion is stopped by seeing the actual analog
output value.
5) Turn Operating condition setting request (Y9) from on to off.