EasyManua.ls Logo

Mitsubishi Electric Q62DAN - 1.2 Functions Added to Function Version B and Later

Mitsubishi Electric Q62DAN
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 - 3 1 - 3
MELSEC-Q
1 OVERVIEW
1.2 Functions Added to Function Version B and Later
(1) Functions added to function version B D/A converter module
The functions added by the function version B D/A converter module are listed
below.
Item Function overview Reference section
Multiple CPU system
compatibility
Compatible with a Multiple CPU system.
A programmable controller CPU of function version B or later are
required.
Section 2.1
Analog output test during
programmable controller
CPU STOP
When the CH
output enable/disable flag is forced on during
programmable controller CPU STOP, the D/A converted value is
output.
Section 3.2.3
Resolution mode
The resolution mode can be changed according to the application, and
a resolution setting can be selected from 1/4000, 1/12000 and 1/16000.
Section 3.2
High resolution mode
status flag (X8)
This turns on when in high resolution mode. Section 3.3
POINT
(1) Refer to Appendix 1.1 for a comparison of functions of the function version.
(2) Refer to Section 2.3 on how to check the function version.
(2) Functions added to function version C D/A converter module
The functions added by the function version C D/A converter module are listed
below.
Item Function overview Reference section
Online module change
You can change the module without stopping the system.
A programmable controller CPU of function version C or later is
required.
Chapter 7
Mode switching that does
not require programmable
controller CPU to be reset
Mode switching setting (buffer memory address 158, 159: Un\G158,
Un\G159) and Operating condition setting request (Y9), the module is
switched between the normal mode and offset/gain setting mode
without the programmable controller CPU being reset.
Section 3.4.12
Using the dedicated instruction (G(P).OFFGAN), the module is
switched between the normal mode and offset/gain setting mode
without the programmable controller CPU being reset.
Appendix 3.1
Using GX Configurator-DA, the module is switched between the normal
mode and offset/gain setting mode without the programmable controller
CPU being reset.
Section 5.6.2

Table of Contents

Related product manuals